Protec Model 600 Desiccant Dehumidifier Offers Unmatched Features
Capacity:
Process air flow rates of 300 to 1125 scfm. Nominal moisture removal of 16 lbs./hr. @75°F/50%RH @600 scfm.
Desiccant Options:
Titanium silica gel, lithium chloride, and molecular sieve options provide efficient operation for any application.
Contact Air Seal System:
Separate process and reactivation air streams at pressures up to 8" W.G., with 5-year life expectancy.
Reactivation Options:
Modulating electrical, steam or gas reactivation.
Low Temperature Operation:
Functions effectively to 40°F. Will not ice-up like refrigeration-based dehumidifiers.
Durability: Welded aluminum housing, durable polyurethane finish, weather-tight access panels. Heavy-duty blowers, drive controls, and electrical components. Suitable for indoor and outdoor use.
Options
Humidistat Control
Moisture Margin Control
Watch Monitoring System
Pre/post Air Treatment
Internal Process Air By-pass
Specifications
Process Air Volume: 600 scfm
Maximum Reactivation Air Volume: 230 scfm
Nominal Moisture Removal: 16 lbs./hr. @ 75°F/50%RH and 600 scfm
Utilities: 208, 230, 460 or 575 volts 3-phase, 60 Hertz (also available with steam or gas reactivation)
Unit Amp Draw: 460/3/60 FLA 16.6
Contact Air Seals: Separate process and reactivation air at pressures up to 8" W.G. with 5-year life expectancy
Filters: Permanent and Washable
Manufacturer: ISO 9001 Certified
Suggested Specification Guide
Dehumidifier shall be of a type proven in satisfactory operation for a minimum of ten years. Dehumidifier shall be of the non-cycling sorption type with a single desiccant, rotary structure. The casing shall be fabricated as a unitized body with welded aluminum construction for maximum strength and durability.
Suitable access panels on both sides of the unit shall allow access for inspection or servicing without disconnecting ducting or electrical wiring. Airflow balancing dampers to be furnished. The dehumidifier shall be designed for continuous operation.
The rotary structure shall be a monolithic fabricated extended surface composite consisting of inert silicates reinforced with uniform diameter glass fibers for maximum strength. The fabricated structure shall be smooth and continuous in the direction of air flow without interruptions or sandwich layers which restrict airflow or create a leakage path at joining surfaces. Desiccant shall not channel, cake or fracture due to repeated temperature and moisture cycling. The materials of construction shall be non-toxic.
Design shall be modular in approach to readily allow connection to accessories such as face and bypass, pre- or post-cool modules. |